+86-312-6775656
HZDZ-P3-tablet type 3-faset strømkvalitetsanalysator

HZDZ-P3-tablet type 3-faset strømkvalitetsanalysator

HZDZ-P3 3 Phase Power Quality Analyzer When it is interfered or contaminated, grid power quality can't reach the national standards, so it has to be targeted on the grid power quality improvement. To understand the actual situation of power quality, you must have the appropriate equipment to...
Product Details ofHZDZ-P3-tablet type 3-faset strømkvalitetsanalysator

 

HZDZ-P3 3-faset strømkvalitetsanalysator


When it is interfered or contaminated, grid power quality can't reach the national standards, so it has to be targeted on the grid power quality improvement. To understand the actual situation of power quality, you must have the appropriate equipment to test and analysis the actual situation. Counter the domestic condition, our company developed the professional power quality analysis instrument, which is suitable for the country.


Tekniske specifikationer

Projekt

Data

Antal målekanaler

Fire spændingskanaler, fire strømkanaler

Måleområde

Spænding

0-900V

Nuværende

Lille klemme: diameter 8mm, 5A/25A (standard)

Mellem klemme: diameter 50 mm, 100A/500A (valgfrit)

Stor klemme: diameter 12550 mm, 400A/2000A (valgfrit)

Fase vinkel

0.000-359.999 degree

Frekvens

42.5-69Hz

Måletrin

Spænding

0.001V

Nuværende

0.0001A

Fase vinkel

0.001 grad

Strøm

aktiv effekt {{0}},01W,reaktiv effekt 0,01Var

Frekvens

0.0001Hz

Spændingsmålenøjagtighed

Mindre end eller lig med 0,1 procent

Strømmålingsnøjagtighed

Mindre end eller lig med 0,3 procent

Fasevinkelmålingsnøjagtighed

Mindre end eller lig med 0,1 grad

Power measurement accuracy

Mindre end eller lig med 0,5 procent

Frequency measurement accuracy

Mindre end eller lig med 0.01Hz

Harmoniske analysetider

2-64 times

Harmonisk spændingsmåling fejl

Harmonic content>1 percent Nominal value: Less than or equal to 1 percent  RD

Harmonic content<1 percent Nominal value: Less than or equal to 0.05 percent FS

Harmonisk strømmålingsfejl

Harmonic content>3 percent Nominal value: Less than or equal to 1 percent RD

Harmonic content<3 percent Nominal value: Less than or equal to 0.05 percent FS

Trefaset spændingsubalancefejl

Mindre end eller lig med 0,2 procent

Trefaset strømubalancefejl

Mindre end eller lig med 0,5 procent

Spændingsudsvings nøjagtighed

5 procent

PST-måletid

10 min

PLT-måletid

2h

PST/PLT målefejl

Mindre end eller lig med 5 procent

Skærm

1280800, Ægte farve LCD

Opladningseffekt

AC220V±15 percent

Frekvens 45Hz-65Hz

Standby timing

Større end eller lig med 10 timer

Værtskraft

<4VA

Isolering

1) The insulation resistance between the voltage, current input terminal and the housing Less than or equal to 100MΩ.

2) Tåler 1,5KV (gyldig værdi) med strømfrekvens på driftsstrømindgang og skallen, som varer et minut.

Huazheng Electric Manufacturing

Customer Visit

Case

Request for quote_

Populære tags: HZDZ-P3 Tablet Type 3 Phase Power Quality Analyzer, Kina, leverandører, producenter, pris, til salg, HZDZ-P3, enfaset strømkvalitetsanalysator

Send forespørgsel

(0/10)

clearall