HZYA-2Z Digital Transformer On Load Switch Tap-Changer Analyzer
HZYA-2Z Digital Transformer On Load Switch Tap-Changer Analyzer
I.Beskrivelse
The on-load tap-changer is the only moving part connected to the transformer circuit. Therefore, the detection of the on-load tap-changer is becoming more and more important. In the "power equipment transfer and preventive test procedures", asked to check the on-load tap-changer action sequence, measurement switching time. The instrument is mainly used to measure the transformer on-load tap-changer transition waveform, transition time, the instantaneous transition resistance, three-phase synchronization and so on.
Instrumentet er meget intelligent, alle kinesiske menu-prompter, enkel betjening. Instrument lille størrelse, let vægt, anti-interferens evne, i høj grad reducere arbejdsintensiteten af webstedets personale, er strømforsyningsenheder, transformer fremstillingsindustrien for at sikre sikker produktion, forbedre produktkvalitet ideelle instrument.
II.Tekniske parametre
Udgangsstrøm: 1.0A, 0.5A 0.2A
Measuring range Transition resistance: 2Ω-20Ω(1.0A) 5Ω-40Ω(0.5A)
20Ω-100Ω(0.2A)
Overgangstid: 0 320ms
Åben kredsløbsspænding: 24V
Measurement accuracy Transition resistance: ± (5 percent reading ± 0.1Ω)
Transition time: ± ({{0}}.1 percent reading ± 0.2ms)
Samplinghastighed på 20kHz
Lagertilstand Lokal lagring
Dimensioner: 340mm 245mm 210mm
Instrumentvægt: 7 kg
III.Anvendelsesbetingelser
Omgivelsestemperatur -10 grader 50 grader
Omgivende luftfugtighed Mindre end eller lig med 85 procent RF
Work Power AC220V±10 percent
Power frequency 50 ± 1Hz



Populære tags: HZYA-2Z Digital Transformer On Load Switch Tap-Changer Analyzer, Kina, leverandører, producenter, pris, til salg HZYA-2Z, oltc analysator, On Load Switch Tap-Changer Analyzer